Customer Support
Helpline:
+44 (0) 1752 894 554
Email Sales:
sales@softstartdirect.com
Email technical:
technical@softstartdirect.com
Our Products
Related Links
DFE

Low Cost, Internally Bypassed Soft Starter
The DFE is Fairford's internally bypassed, non-optimising Soft Starter which is perfect for panel builders and end users alike.
To the user it offers competitive pricing, soft stopping and the removal of high transient currents. To panel builders it is an ideal substitute for a Star/Delta starter because it fits into a similar footprint, thus simplifying installation. It's now available from 22 Amps to 500 Amps
- 22 - 500 Amp
- 11 - 280 kW
- Internally Bypassed
- Low Cost Solution
- Similar Foot Print to Star/Delta Starter
- For Starts per Hour please see product documentation or contact Fairford
DFE Main Features
Internally Bypassed
Reduces cost because when the Soft Starter has reached top of ramp the Thyristors are bypassed, this reduces heat and the size of the cabinet required.
Substitution of Star/Delta Starters
- Lower maintenance costs
- Less stress on auxiliary equipment when starting
- Reduced down time
- Low cost of ownership
Simplified Installation
Rapid build and install time.
No need to change wiring configurations
All six wires of the start delta configuration can be used to minimise installation and design costs.
Competitive with Star/Delta Starters
- Longer life
- Less maintenance
- Lower cost of ownership
Specifications and Ratings
Operational Voltage (Ue) |
230-460VAC rms 3 Phase (-15%+10%) |
Rated Frequency |
50-60 Hz +/- 2Hz |
Index Ratings |
Standard (DFE-02 - DFE-26) AC53b: 3-5: 355 Class 10B (DFE-02 to DFE-26) AC53b: 3.5-12: 708 Standard (DFE-30 – DFE-38) AC53b: 3-5: 355 Class 10B (DFE-30 – DFE-38) AC53b: 3.5-12: 1188 |
Control Supply |
24V DC Supplied externally to terminals X1-X2 |
Soft Start/Stop Control |
24V DC/110V AC galvanically isolated terminals A1-A2 |
Auxiliary Circuits (Relays) |
Run - 13/14, Ready - 23/24. 230VAC 3A, Ac11 |
Indication |
Multifunction LED on the front of the unit |
Start Time |
0.5 to 30 Seconds |
Stop Time |
0 to 30 Seconds |
Power Terminals |
|
IP Rating |
Up to 55kW IP20 |
Ambient Temperature |
0°C to 40°C |
Transport and Storage |
-25°C to +60°C |
Altitude |
1000m. Above 1000m de-rate linearly by 1% of unit FLC per 100m to a maximum altitude of 2000m. |
Humidity |
Max. 85% non-condensing, not exceeding 50% at 40°C |